111
CP 343−2 / CP 343−2 P AS−Interface Master
Release 08/2008
C79000−G8976−C149−04
7
Dealing with Problems / Error Displays
This chapter contains information about special operating states of the CP 343-2. It
is intended to help you to deal with problems.
7.1
Replacing a Defective AS-i Slave/Automatic Address
Programming
Simple Replacement of AS-i Slaves
Using the automatic address programming function, you can replace failed AS-i
slaves extremely simply.
Note
Remember that “automatic address programming” is only possible when the CP
343-2 is in the protected mode and only one AS-i slave has failed.
Slaves with profile CTT5 (multiaddress slaves) do not support automatic address
programming.
The sections below explain how to replace failed AS-i slaves using the automatic
address programming function.
Detecting a Defective AS-i Slave
If the AUP LED is lit (only in the protected mode) this indicates the following:
S
Exactly
one
slave has failed.
S
Automatic address programming by the CP 343-2 is possible.
You can recognize the failed AS-i slave simply because the LED assigned to the
slave flashes on the front panel.
Replacing a Defective AS-i Slave
S
Replace the defective AS-i slave with an
identical
AS-i slave with address
zero (default address).
The CP 343-2 then programs this slave with the address of the original station that
had failed.
The “AUP” display goes off. The LED in the slave display of the CP 343-2 module
indicates that the slave has been included.