Configuration
3.12 Communication with the CPU
Configuration - DNP3
Configuration Manual, 11/2018, C79000-G8976-C508-01
65
Byte 1 "Path status"
Byte 1 shows the status of the connection path (configured connection) to the partner from
the point of view of the local TIM.
A maximum of 2 paths (main and substitute path) to a partner can be configured, see section
Communications options (Page 26).
Both connection paths must start or end on a local TIM.
The byte shows the following:
●
The paths via which the partner can be reached.
●
The path currently being used
●
The TIM interface via which the main path was configured.
●
The TIM interface via which the substitute path was configured.
The path of a connection is specified as a combination of the used interfaces of the TIM and
the status of the path.
Byte assignment
Byte 1 is assigned as follows:
●
Two bits for the interface of the main path
●
Two bits for the interface of the substitute path
●
Two bits for the status of the main path
●
Two bits for the status of the substitute path
Table 3- 2
Assignment of byte 1:
Bits 6 + 7
Bits 4 + 5
Bits 2 + 3
Bits 0 + 1
Configured interface
Path status
Coding for substitute path
Coding for main path
Substitute path (2nd
path)
Main path (1st path)
●
Configured interface
The TIM interfaces "Ethernet 1" (IE1), "Ethernet 2" (IE2), "Ethernet 3" (IE3) and WAN1
are numbered through from 0 . 3 (decimal):
–
0 = Ethernet interface IE1 (X1)
–
1 = Ethernet interface IE2 (X2)
–
2 = Ethernet interface IE3 (X3)
–
3 = Serial interface WAN1 (X4)
Status of bit 5
(7)
Status of bit 4
(6)
Meaning
0
0
Coding for Ethernet interface X1 (decimal: No. 0)
0
1
Coding for Ethernet interface X2 (decimal: no. 1)
1
0
Coding for Ethernet interface X3 (decimal: no. 2)
1
1
Coding for serial interface X4 (decimal: no. 3)