Diagnostics
4.5 SINAUT special diagnostics
Configuration - DNP3
144
Configuration Manual, 11/2018, C79000-G8976-C508-01
The "Transmission Information" list shows all MSC stations along with the following detailed
information stored on the MSC master station when the dialog is opened.
●
Globe icon
The globe icon in this dialog has a the following meaning depending on its color (from the
perspective of the master station):
–
Black and white ( )
The station can be reached online but the displayed data is not up to date. The reason
for this may be that the response to a query was not received, for example due to a
timeout: *
)
–
Green ( )
All the required properties of the network provider are configured. The network
provider can be reached online.
–
Blue and red ( )
The network provider cannot be reached.
*
)
When the "MSC Communication" tab is opened, the icons of all stations are gray. The
change to green or blue and red takes place only after the data has been updated (see
below).
●
Subscriber number
●
Station
●
Signal quality
see below → "Quality of the received signal"
●
Sent current month / Received current month
Sent/received volume of data since the last change of month
Difference between "current count - count previous month" (see below)
–
When the TIM of a DSL station is restarted, the counter is set to 0.
–
When the MD720 of a GPRS station is restarted, the counter is set to 0.
The fields below this show more details of the MSC station selected in the list:
●
Device name
Device name of the TIM
●
Firmware version
TIM firmware version
●
Protocol version
MSC protocol version
The following information is only supplied by GPRS stations with MD720:
●
Signal quality
Relative receive quality
Range: 0..99