WBM of the TIM 1531 IRC
C.6 Maintenance
Configuration - DNP3
174
Configuration Manual, 11/2018, C79000-G8976-C508-01
Note
Do not operate during the update
During the update of the firmware until the TIM restarts, the WBM is not blocked.
Do not perform any operations during this time (e.g. no restart).
Note
Do not switch off the power supply
During activation of the firmware do not switch off the power supply. This avoids the
occurrence of inconsistent statuses.
Firmware
The following information is shown:
●
Firmware version
Version of the firmware currently being used by the TIM.
●
Date
Date the firmware was generated
Firmware update
Download the firmware file to the file system of your connected PC.
●
File
After selecting a firmware file stored on the PC using the "Browse" button, the file name is
displayed here.
●
Browse
Searches the file system of the PC for a firmware file saved there that is intended to be
loaded on the TIM.
●
Load on device
By clicking the button, download the selected firmware file to the TIM.
Note that updating the firmware can take a while. You can recognize the current status of
the firmware download based on the LED pattern.
After updating the firmware the TIM starts up again automatically.
C.6.2
Operating status
Operating statuses
Apart from using this WBM page, you can also execute the functions described below using
the switch of the TIM.