![Siemens SIMATIC NET CP 1243-1 DNP3 Configuration Manual Download Page 110](http://html.mh-extra.com/html/siemens/simatic-net-cp-1243-1-dnp3/simatic-net-cp-1243-1-dnp3_configuration-manual_1265365110.webp)
Configuration
3.20 Configuring data points
Configuration - DNP3
110
Configuration Manual, 11/2018, C79000-G8976-C508-01
The table lists the supported data point types of the modules with the classifications of the
protocol and the compatible S7 data types of the CPU.
Note
Effect of the change of arrays for data points
If an array is modified later, the data point must be recreated.
Data point types
Table 3- 4
Data point types, DNP3 object groups, variants and compatible S7 data types
Format (memory
requirements)
Data point type
DNP3 object
group
[variation]
Direction
S7 data types
Operand area
CP
TIM
Bit
Binary Input
1 [1, 2]
in
Bool
Bool
I, Q, M, DB
Binary Input Event
2 [1, 2]
in
Bool
Bool
I, Q, M, DB
Binary Output
1)
10 [2]
out
Bool
Bool
Q, M, DB
Binary Output Event
1)
11 [1, 2]
out
Bool
Bool
Q, M, DB
Binary Command
12 [1]
out
Bool
Byte
Q, M, DB
Integer (16 bits)
Counter
20 [2]
in
UInt, Word Word
I, Q, M, DB
Frozen Counter
2)
21 [2, 6]
in
UInt, Word Word
I, Q, M, DB
Counter Event
22 [2, 6]
in
UInt, Word Word
I, Q, M, DB
Frozen Counter
Event
3)
23 [2, 6]
in
UInt, Word Word
I, Q, M, DB
Analog Input
30 [2]
in
Int
Int
I, Q, M, DB
Analog Input Event
32 [2]
in
Int
Int
I, Q, M, DB
Analog Output Sta-
tus
4)
40 [2]
out
Int
Int
Q, M, DB
Analog Output
41 [2]
out
Int
Int
Q, M, DB
Analog Output
Event
4)
42 [2, 4]
out
Int
Int
Q, M, DB
Integer (32 bits)
Counter
20 [1]
in
DWord
DWord
I, Q, M, DB
Frozen Counter
2)
21 [1, 5]
in
DWord
DWord
I, Q, M, DB
Counter Event
22 [1, 5]
in
DWord
DWord
I, Q, M, DB
Frozen Counter
Event
3)
23 [1, 5]
in
DWord
DWord
I, Q, M, DB
Analog Input
30 [1]
in
DInt
-
Q, M, DB
Analog Input Event
32 [1]
in
DInt
-
Q, M, DB
Analog Output Sta-
tus
4)
40 [1, 3]
out
DInt
DWord
Q, M, DB
Analog Output
41 [1]
out
DInt
DWord
Q, M, DB
Analog Output
Event
4)
42 [1]
out
DInt
DWord
Q, M, DB