WBM of the TIM 1531 IRC
C.6 Maintenance
Configuration - DNP3
Configuration Manual, 11/2018, C79000-G8976-C508-01
175
The buttons have the following functions:
●
Run a restart
When restarting, existing telecontrol connections are interrupted and cyclic processing
stops. The TIM restarts.
●
Reset to factory settings
Note
Data loss: Note the effects of a reset
Before you reset, note the effects.
Resets the TIM to the factory settings. During this all parameters are reset to the initial
statuses as shipped and the TIM restarts.
If you use an SD card and you want to reset the TIM to the factory settings, you must pull
the SD card (while disconnected from the power) before resetting. If the SD card remains
inserted, the TIM starts up again with the configuration data on the SD card.
Resetting to factory settings: Effect
Note
Configuration data is deleted
Resetting to factory settings deletes all configuration data in the TIM.
●
Deleted data
The following data is deleted by resetting to factory settings:
–
Configured IP addresses of the LAN interfaces X1, X2 and X3
–
All other configuration data in the work memory of the TIM
●
Data not deleted
The following data is not deleted by resetting to factory settings:
–
MAC addresses of the LAN interfaces