![Siemens SIMATIC NET CP 1243-1 DNP3 Configuration Manual Download Page 32](http://html.mh-extra.com/html/siemens/simatic-net-cp-1243-1-dnp3/simatic-net-cp-1243-1-dnp3_configuration-manual_1265365032.webp)
Configuration
3.2 Communication types
Configuration - DNP3
32
Configuration Manual, 11/2018, C79000-G8976-C508-01
These can be:
●
NTP / 123 (UDP)
●
DNS / 53 (UDP)
●
DHCP / 67, 68 (UDP)
●
SINEMA RC Autoconfiguration / 443 (TCP) - can be set
●
SINEMA RC and OpenVPN / 1194 (UDP) - can be set in SINEMA RC
3.2
Communication types
"Communication types"
In this parameter group, you enable the communication capability of the module.
Depending on the module type, you can define the telecontrol protocol and other
communication types.
●
Enable telecontrol communication
Enables telecontrol communication with the communication partners.
●
Protocol type
–
ST7
–
DNP3
–
IEC 60870-5
●
Enable online functions
Enables access to the CPU for the online functions via the CP (diagnostics, loading
project data etc.). If the function is enabled, the engineering station can access the CPU
via the CP.
If the option is disabled, you have no access to the CPU via the CP with the online
functions. Online diagnostics of the CPU with a direct connection to the interface of the
CPU remains possible, however.
●
Enable S7 communication
Enables the functions of S7 communication with a SIMATIC S7 in the module.
If you configure S7 connections to the relevant station, and these run via the module, you
need to enable this option.
●
Activate telecontrol communication via SINEMA Remote Connect
Configurable with:
–
CP 1243-1
–
CP 1243-8 IRC
–
CP 1542SP-1 IRC
For more, see the appendix SINEMA Remote Connect (CP) (Page 161).