Technical specifications
5.5 Ambient conditions
IFP2200 INOX MT ETH
Compact Operating Instructions, 03/2018, A5E42185570-AA
39
5.5.3
Electromagnetic compatibility
Pulse-shaped interference
The following table shows the electromagnetic compatibility of modules with regard to pulse-
shaped interference. This requires the device to meet the specifications and directives for
electrical installation.
Pulse-shaped inter-
ference
Test voltage
Degree of
severity
Electrostatic
discharge
in accordance with
IEC 61000-4-2
Air discharge: 8 kV
3
Contact discharge: 6 kV (front)
Contact discharge: 4 kV (rear)
2
Bursts
(high-speed transient
interference)
in accordance with
IEC 61000-4-4
2 kV power supply cable
2 kV signal cable, > 30 m
1 kV signal cable, < 30 m
3
Powerful single pulse (surge) according to IEC 61000-4-5, external protective circuit is required (see
function manual "SIMATIC S7-1500, ET 200MP, ET 200SP, ET 200AL Designing interference-free
controllers", section 7 "Lightning protection and overvoltage protection") on the Internet
(
https://support.industry.siemens.com/cs/ww/en/view/59193566
).
Asymmetrical
coupling
2 kV power supply cable
DC voltage with protective elements
1
2 kV signal/data cable, > 30 m,
with protective elements as required
1
3
Symmetrical
coupling
1 kV power supply cable
DC voltage with protective elements
1
1 kV signal cable, > 30 m,
with protective elements as required
1
3
1
The following lightning protection element was used during the testing of the Industrial Flat Panel:
Dehn BVT AVD 24" (Order No. 918 422)
Sinusoidal interference
The following table shows the EMC behavior of the modules with respect to sinusoidal
interference. This requires the HMI device to meet the specifications and directives for
electrical installation.
Sinusoidal interfer-
ence
Test values
Degree of
severity
HF radiation
(electromagnetic
fields) according to
IEC 61000-4-3
80% amplitude modulation at 1 kHz
with 10 V/m in the range of 80 MHz to 1 GHz
with 3 V/m in the range 1.4 GHz to 2 GHz
with 1 V/m in the range 2 GHz to 2.7 GHz
3
HF power applied to
lines and line shields
according
IEC 61000-4-6
Test voltage 10 V, with 80% amplitude modulation of 1 kHz
in the 150 kHz to 80 MHz range
3