Installing and connecting the device
3.1 Preparing for installation
IFP2200 INOX MT ETH
16
Compact Operating Instructions, 03/2018, A5E42185570-AA
Mounting in vertical format
You can also install the device in portrait format.
A maximum ambient temperature of +40 °C is permissible for vertical mounting (0° tilt angle);
a maximum of +35 °C is permitted for inclined mounting.
3.1.4
Notes on installation
Mounting cutout
The HMI device can be installed in control cabinets (see table for material thickness). No
special tools are required for mounting. The HMI device can be operated both in landscape
and portrait format with a vertical inclination of up to +/-35°. Due to the surrounding beveling
of the stainless steel front of 45°, liquids are able to drain off even in an inclined installation
position of +/-35°.
The following conditions apply to the mounting cutout:
The front material has to consist of sheet steel or material of a strength that corresponds to
at least the stability of sheet steel.
Mounting cutout
Dimensions
Material thickness
1.5 to 6 mm
Permitted deviation from plane
This condition must be fulfilled for the mounted HMI device.
≤
0.5 mm
Permitted surface roughness in the area of the mounting seal
≤
120 µm (R
z
120)