Technical specifications
5.5 Ambient conditions
IFP2200 INOX MT ETH
40
Compact Operating Instructions, 03/2018, A5E42185570-AA
Emission of radio interference
The following table shows the emitted interference from electromagnetic fields according to
EN 61000-6-4, measured at a distance of 10 m.
Radiated emission (emitted interference)
1 GHz to 3 GHz
< 66 dB peak and < 46 dB average
3 GHz to 6 GHz
< 70 dB peak and < 50 dB average
30 MHz to 230 MHz
< 40 dB (
μ
V/m) quasi-peak
230 MHz to 1000 MHz
< 47 dB (
μ
V/m) quasi-peak
Emission of radio interference voltages
0.150 MHz to 0.5 MHz
< 79 dB quasi-peak and < 66 dB average
0.5 MHz to 30 MHz
< 73 dB quasi-peak and < 60 dB average
5.5.4
Information on insulation tests, protection class and degree of protection
Test voltages
Insulation strength is demonstrated in the type test with the following test voltages in
accordance with IEC 61131-2:
Circuit
Insulation tested with (type test)
Rated voltage U
e
24 V
707 V DC or 500 V AC to other circuits / to ground
Ethernet connector
1500 V AC
Protection class and degree of protection
The device offers the following protection against foreign bodies and water:
Feature
Standard
Degree
Protection class
EN 61131-2
Protection class III
Degree of protection, front
EN 60529
IP69
ISO 20653
IPX6K
Degree of protection, rear
EN 60529
IP20
Touch protection test with standard test probes.
There is no protection against ingress by water.
The IP degrees of protection and enclosure type can only be ensured if the mounting seal is
in full contact with the cutout. Read the corresponding information in section
"Notes on installation (Page 16)".
Degree of pollution / overvoltage category according to IEC 61131
●
Degree of pollution 2
●
Overvoltage category II