Parameterizing the Mobile Panel
5.15 Functions for service and commissioning
Mobile Panels 2nd Generation
154
Operating Instructions, 09/2018, A5E33876626-AC
Icon Status
Alarm
Meaning
Upgrade
Runtime
upgrade
Runtime version on the HMI device is older than the
Runtime version of the project, versions are compatible,
upgrade of Runtime version on the HMI device is
optional.
Upgrade
Firmware
upgrade
Firmware version on the HMI device is older than the
firmware version of the project, versions are compatible,
upgrade of firmware on the HMI device is optional.
Downgrade Runtime
downgrade
Runtime version on the HMI device is newer than the
Runtime version of the project, versions are compatible,
downgrade of Runtime version on the HMI device is
optional.
Downgrade Firmware
downgrade
Firmware version on the HMI device is newer than the
firmware version of the project, versions are compatible,
downgrade of firmware on the HMI device is optional.
–
Alarms of type "Error" with option:
Icon Status
Alarm
Meaning
Upgrade
Runtime upgrade Runtime version on the HMI device is older than the
Runtime version of the project, versions are
incompatible, upgrade of Runtime version on the HMI
device is required.
Upgrade
Firmware
upgrade
Firmware version on the HMI device is older than the
firmware version of the project, versions are
incompatible, upgrade of firmware on the HMI device
is required.
Downgrade Runtime
downgrade
Runtime version on the HMI device is newer than the
Runtime version of the project, versions are
incompatible, downgrade of Runtime version on the
HMI device is required.
Downgrade Firmware
downgrade
Firmware version on the HMI device is newer than
the firmware version of the project, versions are
incompatible, downgrade of firmware on the HMI
device is optional.
Download Runtime
download
There is no Runtime software on the HMI device, e.g.
after update of the operating system. Runtime
software must be downloaded.
NOTICE
Data loss
If you enable the "Firmware upgrade" or "Firmware downgrade" option, the operating
system of the HMI device will be updated. All data on the HMI device, including the
HMI device password, is deleted in the process. Settings in the Start Center are
retained. License keys are backed up to the external storage medium before the
operating system update.
Back up your data before the load operation, if necessary.
The project can be loaded into the HMI device if no "Error..."-type alarms occur or if all
"Upgrade/Downgrade" options were enabled for the "Error..."-type alarms.