System commissioning
5.2 Accepting effective ranges and transponders
Fail-safe operation of the Mobile Panel 277F IWLAN
Function Manual, 08/2008, 6AV6691-1FQ01-2AB0
81
9.
Select the next effective range in the list.
10.
Repeat steps 4 to 7 for all transponders assigned to this effective range.
11.
Verify all additional effective ranges in the list to the left.
12.
When you have successfully verified all effective ranges, touch the "Calculate" button.
The HMI device calculates the CRC checksum. The CRC checksum is displayed in the
"CRC" box.
13.
Open the project in WinCC flexible ES.
14.
Enter the checksum in the "Effective ranges" editor.
15.
Transfer the project to the HMI device again.
Result
The project can now be used for operating and monitoring the plant.