20
• Place the software alarms into position (paragraph 2.5)
• Place the hardware alarms into position (see machine handbook)
K3
Cycles menu
B1
This page is used to select the various
functions to run the cycles and to start
or stop a programme.
B2
Program edit
: (1)
Loop table
: (2)
Save program
: (3)
Load program
: (4)
B3
Delete program
: (5)
Repetition
: (6)
Ver. curr. progr.
: (7)
to set a programme
to set a loop (§4.4)
to save a programme (§4.5)
to load a programme into the memory
(§4.6)
to delete a programme already memo-
rized (§4.7)
to define the number of times a pro-
gramme has to be repeated (§4.8)
to visualize a set cycle (§4.9)
B4
Choice
#
Start progr.
STOP
Monitoring
: OFF
to select a function (from 1 to 7)
to start or stop a programme
when it is switched ON, the current seg-
ment is visualized only while the cycle is
being carried out
1
KEYS
DISPLAY
FUNCTIONS
To select option 1
“Edita programme”
EDIT PROGRAM
< ESC > Prev.menu
Segment N. 1
B5
B6
hh : mm : ss
Durat.
0 : 0 : 0
Wait duration
: OFF
These data must not be set for the first
segment;
The first segment must be carried out at
maximum speed.
4.3
HOW TO SET A PROGRAMME
The cycle shown in the graph will be set as an example here below.
B7
Channel 1
Control
: OFF
Wait set point
: OFF
Max speed
: OFF
there are two channels for each segment:
Channel 1: to set the temperature
Channel 2: to set the humidity
when it is switched ON, temperature control is
enabled
when it is switched ON, it moves on to the next
segment only when the set set point is reached.
When it is switched OFF, it moves on to the
next segment after the set time, whether the
set value has been reached or not.
When segment switch ON, it must be
carry at the maximum speed
The temperature values and other pa-
rameters are set on this page
ENTER
Summary of Contents for OP7
Page 3: ......