Connect external components
Desk call station PT2001-A1
7
92 | 121
A6V11940317_en--_a
If the DC 24 V is used for other external devices, a 1 A fuse is required for each
device.
7.1.3.2 Redundant power supply from a cabinet
Fig. 52: PT2001-A1 redundant power supply from a cabinet
1 Novigo Core cabinet
2 External 'Desk call station (19 buttons)' PT2001-A1 with accessories
3 DC/DC converter 'MeanWell SD-50B-24 DC/DC' PCA2011-A1 or 'MeanWell
SD-100B-24 DC/DC' PCA2018-A1
4 'Ground fault monitoring (24V)' PCA2001-A1
5 Fuse 1 A
6 'Call station interface (redundant)' PTO2009-A1. See
7 DC 24 V wiring to 'Desk call station (19 buttons)' PT2001-A1 or other devices
A ground fault monitor PCA2001-A1 must be used when the PT2001-A1 is
powered from a cabinet with a DC/ DC converter PCA2011-A1 or PCA2018-A1.
If the DC 24 V is used for other external devices, a 1 A fuse is required for each
device.
A PTO2009-A1 must be used to connect the PT2001-A1 with 2 separate DC 24 V
cables from one cabinet or different cabinets. Each DC 24 V cable requires a 1 A
fuse mounted in the cabinet.
7.1.4 Connect PACE-Net Ethernet
The PT2001-A1 provides 2 Ethernet sockets at the rear of the housing. Always
connect port A (ETH A) with an Ethernet switch.
A redundant Ethernet connection can also be established by connecting socket
port B (ETH B) with an Ethernet switch. It can be the same switch or, for higher
redundancy, another Ethernet switch in the system. If the connection on port A
fails, the PT2001-A1 uses automatically port B for the communication.
PT2001
DC/DC
PCA2011
PCA2018
Ground Fault
PCA2001
Fuse
DC 24 V
DC 24 V
Fuse
DC 24 V
Interf.
Redund.
PTO2009
Cabinet
1
1
1
2
1
3
1
4
1
5
1
6
1
7
1
5
1
7