Mounting/Installation
Wire the mains supply line
4
32 | 121
A6V11940317_en--_a
4.5.2 Mains connection PC1002
The 230 V mains connection of the 'Voice alarm panel Core 1000' PC1002-A2 is
divided into 2 connectors: the mains connector 'X100' and the mains connector
'X102'. The 'X100' is used to connect the mains connection and connect the mains
filter. It is in the upper left of the cabinet. The 'X102' is connected to the output of
the mains filter and is used to supply the internal components with 230 V. The
power supply, the mains filter, 2 amplifiers and the PE to the cabinet are already
pre-assembled.
4.5.2.1 Mains connector 'X100' on PC1002
Fig. 5: PC1002-A2 mains connector 'X100' with pre-assembled wiring
Connection to the mains input filter; pre-assembled
X100
Terminal block for the mains supply connection
Mains connector - 'X100'
Pin
Designator Connection
Color
Description
1
L1
Outer conductor
Brown
Mains connection
2
L1
Outer conductor
Brown
Pre-assembled; mains filter
3
N
Neutral conductor
Blue
Mains connection
4
N
Neutral conductor
Blue
Pre-assembled; mains filter
5
PE
Protective conductor
Yellow/green
-
6
PE
Protective conductor
Yellow/green
Pre-assembled; cabinet
7
PE
Protective conductor
Yellow/green
-
8
PE
Protective conductor
Yellow/green
-
9
PE
Protective conductor
Yellow/green
Mains connection
10
PE
Protective conductor
Yellow/green
Pre-assembled; mains filter
Table 2: PC1002-A2 mains connector - 'X100'
Follow the steps below to wire the mains supply line:
1.
Connect the protective conductor with the yellow/green wire to the free 'PE'
ground terminal.
2.
Connect the blue neutral conductor to the terminal 'N'.
3.
Connect the brown outer conductor to the terminal 'L1'.