Mounting/Installation
24 V connection to the power supply
4
34 | 121
A6V11940317_en--_a
4.6 24 V connection to the power supply
The 24 V is required on the digital audio matrix board with DC 24 V power. It is
connected to the power supply via the 'PS-24V' connector. An earth connection to
the cabinet is required for a proper work of the digital audio matrix board. The
power supply reports a general fault status and an AC fault via the 'PS-Fault'
connector. These connectors are located in the inputs/outputs area on the lower
left corner of the board. All connections are pre-assembled.
Fig. 7: PC100x-A2 power supply connector 'PS-24V'
Power supply connector - 'PS-24V'
Pin
Description
Remark
1
DC 24 V +
Red
2
DC 24 V 1
Black
Table 4: PC100x-A2 power supply connector - 'PS-24V'
Power supply connector - 'PS-Fault'
Pin
Description
Remark
Function
1
Fault
Green
Power supply fault
2
AC
Blue
AC 230 V fault
3
10 V
Red
10 V reference voltage to
the power supply
Table 5: PC100x-A2 power supply connector - 'PS-Fault'
The power supply fault contact is usually closed and will open in case of a fault.
Earth connector
Pin
Description
Remark
Function
1
Earth
Yellow/green
Connect to the cabinet earth
Table 6: PC100x-A2 earth connector