Install internal components
Operating unit and call stations PT1002-A1
6
A6V11940317_en--_a
71 | 121
6.2.2 Configuration with the ID-Switch
The ID-Switch must be set to the correct values to identify the components on the
'PACE-Bus' (RS485). The ID must be unique on one 'PACE-Bus' (RS485).
1
2
3
4
ID
Description
0
0
0
0
-
Not allowed
1
0
0
0
-
Not allowed
0
1
0
0
2
-
1
1
0
0
3
-
0
0
1
0
4
-
1
0
1
0
5
-
0
1
1
0
6
-
1
1
1
0
7
-
0
0
0
1
8
-
1
0
0
1
9
-
0
1
0
1
10
-
1
1
0
1
11
-
0
0
1
1
12
-
1
0
1
1
13
-
0
1
1
1
14
-
1
1
1
1
15
-
Table 39: PT1002-A1 set RS485 address with ID switches
● 0 = OFF
● 1 = ON