Mounting/Installation
Wire the mains supply line
4
A6V11940317_en--_a
31 | 121
4.5.1 Mains connection PC1001
The 230 V mains connector of the 'Voice alarm panel Core 400' PC1001-A2 is in
the upper right of the cabinet. The power supply and the PE in the cabinet are
already pre-assembled.
Fig. 4: PC1001-A2 mains connector with pre-assembled wiring
Connection to the power supply; pre-assembled
PE connection to the cabinet; pre-assembled
'X100'
Terminal block for the mains supply connection
Mains connector - 'X100'
Pin
Designator Connection
Color
Description
1
L1
Outer conductor
Brown
Mains connection
2
L1
Outer conductor
Brown
Pre-assembled; power supply
3
N
Neutral conductor
Blue
Mains connection
4
N
Neutral conductor
Blue
Pre-assembled; power supply
5
PE
Protective conductor
Yellow/green
-
6
PE
Protective conductor
Yellow/green
Pre-assembled; power supply
7
PE
Protective conductor
Yellow/green
-
8
PE
Protective conductor
Yellow/green
Pre-assembled; cabinet
9
PE
Protective conductor
Yellow/green
-
10
PE
Protective conductor
Yellow/green
-
11
PE
Protective conductor
Yellow/green
Mains connection
12
PE
Protective conductor
Yellow/green
Pre-assembled; cabinet
Table 1: PC1001-A2 mains connector - 'X100'
Follow the steps below to wire the mains supply line:
1.
Connect the protective conductor with the yellow/green wire to the free 'PE'
ground terminal.
2.
Connect the blue neutral conductor to the terminal 'N'.
3.
Connect the brown outer conductor to the terminal 'L1'.