background image

Rev.

 

1.0

 

 

                                                      

Entero

®

 

Voice

 

Alarm

 

system

 

….

    

 

 

 

 

 

 

 

 

 

 

 

 

 

 

    

     

Entero®

 

ESC

 

installation

 

menu

 

guide

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 

  

 

 

             

   

 

 
 
 

Summary of Contents for Entero ESC

Page 1: ...Rev 1 0 Entero Voice Alarm system Entero ESC installation menu guide ...

Page 2: ...ENTERO ESC INSTALLATION MENU GUIDE 2 The manufacturer reserves specification privileges Information in this manual is subject to change without prior notice or obligation ...

Page 3: ...ntero Evacuation panel and Fire panel 5 1 3 Entero ESA Power Amplifier 6 1 4 Entero EPC Emergency Power Controller 6 2 Indicators and controls access level 2 7 2 1 Entero ESC Emergency System Controller 7 2 2 Main screen 8 2 3 System menu 8 3 System configuration access level 3 11 4 Entero Fire Panel and Evacuation Panel 20 Appendix Error messages 23 ...

Page 4: ...ACIE in accordance with the manufacturer s published instructions and data Access level 4 For persons who are trained and authorized by the manufacturer to either repair the VACIE or alter its firmware thereby changing its basic mode of operation Accessibility of indications and controls at Access level 1 All mandatory indications Voice Alarm condition General errors System faults and Power status...

Page 5: ...hone announcement is active in the Voice Alarm system 1 2 Entero Evacuation panel and Fire panel 1 230Vac GREEN indicates the 230 Vac power status when OFF the power source is disconnected or the unit is not yet calibrated 48 Vdc indicator also OFF 2 48Vdc GREEN indicates the 48 Vdc power status when OFF the power source is disconnected or the unit is not yet calibrated 230 Vac indicator also OFF ...

Page 6: ...ay not be operating anymore 1 4 Entero EPC Emergency Power Controller 1 230Vac INPUT GREEN YELLOW when this indicator is GREEN it shows a correct operating 230 Vac mains power input when the indicator is changed to YELLOW there is an error on the 230 Vac input 2 48Vdc INPUT GREEN YELLOW when this indicator is GREEN it shows a correct operating 48 Vdc battery power input when the indicator is chang...

Page 7: ...s and the number of outputs in test mode Different menu items are available in the System menu ENTERO M1 UNIT OK AC Power 230V OK DC Power 48V OK 48 3V Communication OK Confirmed errors 0 0 Outputs in test mode 0 12 SYSTEM MENU 2 Indicators show the status of POWER SYSTEM FAULTS GENERAL ERRORS and ALARM See also Indicators access level 1 above for more details 3 Navigation buttons use the navigati...

Page 8: ...r indicator test Reset error RETURN System overview System overview shows a list of all components like amplifiers loudspeakers lines error contacts emergency panels and other which have been found during the calibration routine of the system SYSTEM OVERVIEW Speakerline1 No Amp found Speakerline2 A 98W B 30W Speakerline3 A 250W B 125W Speakerline4 A B Opn L Speakerline5 A Opn L B 35W Speakerline6 ...

Page 9: ... and press OK to acknowledge the error To leave this window without acknowledging the error press OK to return when NO is displayed Installation menu See chapter System configuration access level 3 for more details Ext Sig Audio not installed EPC error in installed Ext error in installed Mains error in installed Power 48Vdc installed Wallcontr 1 not installed Wallcontr 2 not installed Wallcontr 3 ...

Page 10: ...ed off RESET ERROR M1 L5 A open Line error M1 Evacpanel4 MicLine2 reset M1 Slave1 com reset M1 L12 B open Line error M1 Firepanel1 MicLine1 reset RETURN Use the up down buttons to select the error and press OK the following menu will appear RESET ERROR M1 L5 Aopen Line error Reset this error NO Use to change press OK To reset the error use the up button to change from NO to YES and press OK To lea...

Page 11: ...displayed Installation menu 1 System overview 2 Test mode overview 3 Unit setup 4 Emergency panel setup M1 5 Battery 6 Rack master slave settings 7 Calibrate whole unit 8 Error log 9 Clear error log 10 Language selection 11 Factory restore 12 Change password RETURN 1 System overview System overview shows a list of all components like amplifiers loudspeakers lines error contacts emergency panels an...

Page 12: ...ut 10 Input Input 11 Input Input 12 Input Return Use the up and down buttons to select an input and press OK the following will be displayed Input 1 Input Input sensitivity 0dB Input gain 0dB RETURN Input sensitivity To change the input sensitivity press OK the 0 dB value will now highlight Use the up and down buttons to change to 10 dB 0 dB or 3dB Press OK again to store the new value Input Gain ...

Page 13: ... RETURN Output Gain To adjust the output gain 80 to 6 dB use the up and down buttons to select the settings and press OK to select value use up and down to change value and press OK to store Emergency Gain To adjust the level of the emergency signal 80 to 6 dB routed to this output only use the up and down buttons to select this menu item and press OK to select value use up and down to change valu...

Page 14: ... Deviation 1k 50W Clear calibration Press OK Calibrate output Press OK RETURN Speaker line in test mode To temporary turn off speaker line monitoring press the OK button to switch from NO to YES to put the output into test mode no errors will be reported In case a short circuit occurs on the line the line will still be disconnected If the amplifier fails which powers this line it will switch to a ...

Page 15: ...wn button to go to the next menu line Clear calibration Press OK to clear a calibrated speaker line Use the up and down button to change NO to YES and press OK to clear and return to the previous menu position Clear this speaker line NO Use up down to change press OK Use the down button to go to the next menu line Calibrate output Press OK to calibrate speaker lines connected to this output Use th...

Page 16: ... line connected 100V or low impedance In case an output needs to be cleared at the same time select CLR For all other items select YES or NO 3 3 Calibrate Unit Select all NO Output 1 100V Output 2 CLR Output 3 L Imp Output 4 YES Output 5 NO Output 6 NO Output 7 NO Output 8 NO Output 9 NO Output 10 NO Output 11 NO Output 12 NO Emergency panels NO ExtContacts 48Volt DC NO Slaves NO Calibrate selecte...

Page 17: ...gency panel bus 2 4dB Ext signal input 3dB RETURN Use the up and down buttons to select Alarm message 1 or 2 or one of the emergency inputs and press OK to select the current gain value use the up and down buttons to change this value and press OK to store 5 Battery The battery menu displays the actual voltage of the secondary power source connected to the Entero ESC 5 Battery Battery voltage 48 5...

Page 18: ...el4 MicLine2 reset M1 Slave1 com reset M1 L12 B open Line error M1 Firepanel1 MicLine1 reset RETURN Use the up and down buttons to select an active error and press OK 8 Error log M1 L5 A open Line error Reset this error NO Use up down to change press OK To reset the error use the up and down button to switch between NO and YES if YES is selected press OK to reset 9 Clear error log Enter this menu ...

Page 19: ... restore the unit to factory default settings 11 Factory restore Factory restore this unit NO Use up down to change press OK Use the up and down button to switch between NO and YES if YES is selected press OK to perform a factory restore 12 Change password Enter this menu to change the password to enter the installation menu Installation menu Enter new password 0000 Use up down to change press OK ...

Page 20: ...iority 1 Fire Panel microphone 2 Evacuation Panel microphone 3 Fire Detection System interface mic line input 4 Fire Panel alarm message s 5 Evacuation Panel alarm message s 6 Fire Detection System interface 7 External Audio input NOTE the Fire Detection System interface and the External Audio input have no manual controls and are therefore not covered in this manual Fire Evacuation Panel main con...

Page 21: ...and D buttons when the code is right the Panel Disabled indicator will turn OFF 2 Alarm zone selection alarm zones can be selected in different ways a Press the ALL ZONES button to select all alarm zones or b Press the A B C or D button if these are pre configured with a group of alarm zones or c Press 1 or more zones on the 12 button expansion card NOTE the corresponding indicator will illuminate...

Page 22: ...vated message from the other emergency panel will stop the Alarm Zone selection will be remembered in the background the ALARM indicator will stay ON 3 Press Pause Alarm to temporary silence this panel this allows the user to select new Alarm zones if Pause Alarm is not selected at this stage and one presses an alarm zone button directly the alarm message will immediately play in that group of ala...

Page 23: ... B Short Circuit error a short circuit is found on the line the line will be disconnected automatically Lxx A Open Line error the loudspeaker line is disconnected Lxx B Open Line error the loudspeaker line is disconnected Lxx Short to Earth Line A B a short circuit to Earth is found the line will be disconnected automatically Lxx A 1 KHz Impedance error an impedance deviation is found on the line ...

Page 24: ...above error contacts is also monitored the following error messages indicate a failure of this connection not the status of the error input itself Connection failures to Possible error description Mains error input Mains Con short error line to error contact is shorted Mains Con open error line to contact is open External error input Ext Con short error line to ext error contact is shorted Ext Con...