182/327
Building Technologies
Basic Documentation LMV5...
CC1P7550en
9 Commissioning instructions for the LMV5
22.05.2018
PG
= 30 mbar
PW = 15
mbar
Patm = 1013 mbar
V
= 3 l
QLeck = 50 l/h
(30 - 15) mbar
•
3 l
•
3600 s / h
t Test =
=
3,2 s
1013 mbar
•
50 l/h
Result:
The test time to be set is 4 seconds
PG
= 30 mbar
PW = 15
mbar
Patm = 1013 mbar
V
= 3 l
tTest = 4 s
(30 - 15) mbar
•
3 l
•
3600 s/h
Q Leck =
=
40,0 l/h
1013 mbar
•
4 s
Result:
The detected leakage rate is 40 l/h
Example 1 (calculation
of test time)
Example 2 (determination
of detectable leakage
rate)