7.8 Limitation of repetitions (can be
parameterized)
If the flame is lost during operation, a maximum of 3 repetitions per controlled startup
can be performed via control thermostat/pressurestat, or else a non-alterable lockout
will be initiated. Counting of repetitions is restarted each time a controlled startup via
control thermostat/pressurestat takes place.
Factory setting: No repetition in the event of loss of flame during operation.
Ε
Note!
In the event of repetition due to loss of flame during operation, a flame signal must be
produced at the end of the safety time; if not, the unit will initiate a non-alterable
lockout.
8 PC software ACS410
8.1 Duty of PC software
The PC software is a component of the LMO39… system and serves primarily as an
operator module for the following basic tasks:
∂
Visualization of system state with the following data:
- Parameters
- Process data
∂
Configuration and parameterization of the basic unit (individual parameters)
∂
Reset
Ε
For operating and commissioning instructions, see Installation and Operating
Instructions J7352.