56/61
Building Technologies
Basic Documentation LMO39…
CC1P7154en
21 Parameter list
15.03.2018
21 Parameter list
Parameter
number
Parameter
Edit
Value range
Increment
Default setting
Password level
reading from
level
Password level
writing from level
Min.
Max.
Internal parameters
41
Heating engineer’s password (4 characters)
Edit
xxxx
xxxx
1
---
---
OEM
42
OEM’s password (5 characters)
Edit
xxxxx
xxxxx
1
---
---
OEM
General
102
Identification date
Read only
---
---
---
---
Info
---
103
Identification number
Read only
0
9999
1
0
Info
---
113
Burner identification
AZL2:
Readable
ACS410:
Selectable
0
99999999
1
burnEr Id
Info
OEM via ACS410
164
Number of startups
Resettable
0
999999
1
0
Info
Info
166
Total number of startups
Read only
0
999999
1
0
Info
---
Burner control
265
Prepurge time
Edit
0 s
1237.005 s
4.851 s
0 s
SO
OEM
266
Preignition time
Edit
0 s
1237.005 s
4.851 s
29.106 s
SO
OEM
267
Safety time
Edit
0 s
14.994 s
0.147 s
4.557 s
SO
OEM
270
Interval: Flame ON until fuel valve 2 (BV2) release
Edit
0 s
1237.005 s
4.851 s
4.851 s
SO
OEM
274
Postpurge time
Edit
0 s
1237.005 s
4.851 s
0 s
SO
OEM
280
Repetition limit value loss of flame or no flame at the end of safety time
0 = none
1 = none
2 = 1 x repetition
3 = 2 x repetition
4 = 3 x repetition
Edit
0
4
1
1
SO
OEM
295
Postignition time
Edit
0 s
14.994 s
0.147 s
4.41 s
SO
OEM
296
Timeout oil preheater
Edit
0 s
1237.005 s
4.851 s
596.673 s
SO
OEM