13 Operation via AZL2
24.07.2020
13.6 Info
level
13.6.1
Display of info level
/reset
1…3 s
Press
/reset
until
InFo
appears.
When releasing
/reset
, you are on the info level.
The info level displays information about the LME7 and operation in general.
Note!
On the info level, you can press
or
to display the next or the previous parameter.
In place of the
button, you can also press
/reset
for <1 second.
Note!
You can press
ESC
or
/reset
for >8 seconds to return to the normal display.
P
V
h min s
%
B
ild
27e
/0
8
07
Parameter
Parameter value
Figure 21: Info level
Note!
No change of value on the info level.
If the display shows
._._
together with the parameter,
the value may consist of more than 5 digits.
When pressing
/reset
for >1 second and <3 seconds, the
value will be displayed.
By pressing
/reset
for >3 seconds or
ESC
, you
return to the selection of the parameter no. (parameter
number blinks).
No.
Parameter
Info level
102 Identification
date
103 Identification
number
113 Burner
identification
123
Minimum output control step
140
Mode display for the 7-segment display
1 = standard (program phase)
2 = flame 1 (QRA / ION)
3 = flame 2 (QRB / QRC)
not used
4 = active power (power value)
164
Number of startups resettable
166
Total number of startups
170.00
Switching cycles relay K12
170.01
Switching cycles relay K11
170.02
Switching cycles relay K2
170.03
Switching cycles relay K1
171
Signaling of “Switching cycle exceeded” for one of
the relay contact counters (parameters 170.00 to
170.03)
→
not active
End