61/116
Smart Infrastructure
Basic Documentation LME7...
CC1P7105en
11 Multistage or modulating mode with actuator
24.07.2020
User limitations / application examples
Application
Typical resolution
Typical modulation range
LME73
Controller with
3 position control
Actuator control
via LME73
7105z19e/0912
- pulse lengths min. 150 ms
- approx. 0.5°
- with 30 s running time
0...90° with 50 Hz
1 : 30 / 1 : 50
For boiler and
process heat
LME73
Controller with
analog control
Actuator control
via LME73
710
5z
20e/
091
2
Feedback potentiometer
4...20 mA
DC 0...10 V
0...135 Ohm
See table
Typical
actuator values and
settings
.
- approx. 2...3°
- with 30 s running time
0...90° with 50 Hz
1 : 10 / 1 : 15
For boiler and
process heat with
lower resolution
LME71
LME73
Controller
Actuator
control
7105z21e/0912
analog
4...20 mA
DC 0...10 V
0...135 Ohm
Release
Fuel valve
Resolution depending on
controller.
- 0.5...2° / 0.5...3°
- with 30 s running time
0...90° with 50 Hz
1 : 10 / 1 : 50
depending on controller
For boiler and
process heat
Note!
If the value set for parameter 123 is too small, the actuator oscillates about the
setpoint, leading to more running cycles, increased switching frequency and more wear
and tear.