Basic Documentation LME7...
CC1P7105en
13 Operation via AZL2
24.07.2020
List of phase display (display depending on program)
Note
Display depending on the PME7, refer to
User Documentation A7105.x
.
Phase number
AZL2 display
Function
Standby
OFF
Standby, waiting for heat request
Ph08
Power ON / test phase (e.g. detector test)
Startup
Ph21
Safety valve ON, air pressure switch test / POC test (timeout / locking after 5 seconds),
actuator opens in low-fire position / CLOSE position
Ph22
Fan motor ON and air pressure switch test / settling time
Ph24
Actuator travels to the prepurge position
Ph30
Prepurging
Ph36
Actuator closes until ignition load / low-fire is reached, and
parameter 259.02: Actuator opens to a position > ignition load
Ph38
Preignition
Ph40
1st safety time / ignition transformer ON
Ph42
Safety time (ignition transformer OFF), flame check
Ph44
Interval: End of safety time and fuel valve V1 ON
Interval: End of safety time and load controller release
Interval: End of safety time and fuel valve V2 ON
Ph50
2nd safety time
Ph54
Parameter 259.01: Actuator opens to a position > low-fire
Ph54
Parameter 260: Actuator closes until low-fire position is reached
oP:P1
Interval to release of preset load controller (analog or 3-position step input)
Operation
oP:xx
Operation, modulating operation
oP:P1
Operation first stage
oP:P2
Operation second stage
Shutdown
Ph10
Actuator travels to the CLOSED position (home run)
Ph72
Actuator opens until high-fire position / operation shutdown is reached
Ph74
Postpurging
Valve proving
Ph80
Test space evacuating
Ph81
Test time atmospheric pressure
Ph82
Test space filling
Ph83
Test time gas pressure
Waiting phases (start prevention)
Ph01
Undervoltage / overvoltage
Ph02
Safety shutdown, followed by a non-alterable lockout with interlocking
e.g. safety loop open
Ph04
Extraneous light on burner startup (timeout / locking after 30 seconds)
Ph90
Pressure switch-min open
safety shutdown / non-alterable lockout with interlocking
Non-alterable lockout
LOC
Lockout phase