15 Operation via internal LED
24.07.2020
15.6 Initial startup with a new PME7 or in case of
replacement of the PME7
Alternately
rSt
and
PrC
are displayed alternately.
The replacement of the PME7 is displayed.
The signal lamp lights up alternately, once red and twice
yellow.
nfo
>3 s
Press
nfo
(for >3 seconds) to start data download from the
PME7. The signal lamp flashes yellow. A short flash of the
yellow signal lamp indicates that 3 seconds have passed.
Note:
If you press
nfo
for <3 seconds, data download does not
start. To start the restore process again, the LME7 must be
reset by switching mains ON/OFF.
Display shows
run
during download (restore process) of the
program sequence.
Alternately
Display shows
alternately
End
and
rSt
.
Display shows the end of data exchange.
Signal lamp blinks red.
After 2 minutes, the LME7 changes to
Loc 138
LC
D
B
ild
0
6
/090
8
Alternately
After the restore process, the LME7 is automatically in the
lockout position (Loc 138) and must be reset for operation.