Function Blocks - FM 458-1 DP
5-1
Edition 12.2004
5
SIMOLINK drive coupling
5.1 @SL SIMOLINK central block
@SL
Hardware address SLB
―
GV TAD
YF
I
―
Error status of the block
Operating mode
―
I MOD NCP
I
―
No. of nodes
Node address
―
I ASL NCY
DI
―
No. of cycles
Send power
―
I POW NOR
DI
―
No. of overruns
Filling-up the telegram gaps
―
BO FIL
NTO
DI
―
No. of timeouts
Use PCI Copy
―
BO DM
NCR
DI
―
No. of CRC errors
Max. blocksize
―
I NSL NDM
DI
―
No. of the defective module
Enable the drive interface
―
BO EN
CO1
DI
―
No. of waiting cycles
CO2
DI
―
No. of CO1 overruns
QF
BO
―
Group error bit
The @SL central block allows the initialization and monitoring of
communications with an SLB module.
An SLB module is a system hardware component, which can be an ITSL-
, an EXM 448-1 module or an optional SLB (
S
IMO
L
INK
B
oard) of the
ITSL module.
The @SL central block may only be configured in a cyclic task and once
per SIMOLINK ring.
The following parameters must be set for an SLB module:
•
Hardware address SLB (TAD)
•
Operating mode (MOD)
•
Node address (ASL), only relevant when operating mode 0 is selected
•
Send power (POW) for the SLB module
1. The @SL central block executes the following steps while the system
is being initialized:
−
Checks the validity of the value ranges at the input connections
−
Checks whether additional @SL central blocks have been
configured at the same hardware address (input TAD)
−
Initializes the SLB module corresponding to the data at the
initialization connections
Symbol
Brief description
Mode of operation