SIMOLINK drive coupling
Function Blocks - FM 458-1 DP
5-11
Edition 12.2004
5.3 SLD SIMOLINK delta evaluation
SLD
Hardware address SLB
―
GV TAD
DAT
DI
―
Delta time
DMX
DI
―
Delta time, max.
DMN
DI
―
Delta time, min.
SEQ
I
―
Sequence number
YF
I
―
Block error status
QF
BO
―
Group error bit
A sampling time failure can be detected using function block SLD. The
counter status is interrogated at each SYNC interrupt (this is generated at
the end of every telegram cycle). The block can calculate and output the
difference to the old (previous) value.
The blocks reads the interrogated value of the counter and generates the
difference to the value which was saved in the old (previous) cycle. This
value is output at DT.
The minimum and maximum values of DT are kept for monitoring
purposes.
TAD
SLB hardware address (name of the SLB module), which can be
configured in HWConfig
DT
Delta time
Difference to the last SIMOLINK cycle duration
(default: 0)
DMX
Delta time, max.
Maximum value of DT
(default: 0)
DMN
Delta time, min.
Minimum value of DT
(default: 0)
SEQ
Sequence number
Number of the block in the SIMOLINK block sequence
This value provides information as to whether the block was correctly
initialized.
(default: 0)
YF
Error status of the block
YF=0
no error, YF > 0 refer to coded error output @SL
(default: 0)
QF
Group error bit
QF=0 no error, QF=1 for error (if YF
≠
0)
(default: 0)
Computation time [µs]
FM 458-1 DP
19,8
Can be inserted online
No
Can be configured in
Interrupt tasks
Cyclic tasks
Executed in
Initialization mode
Normal mode
Special features
-
Symbol
Brief description
Mode of operation
I/O
Configuringdata