Parameter data record
A.1 Parameter assignment and structure of the parameter data record
Digital output module DQ 4x24VDC/2A HS (6ES7132-6BD20-0DA0)
Manual, 03/2015, A5E34944434-AA
43
Codes for time period of the pulse width modulation
The table below contains the codes for the time period of the pulse width modulation of the
digital output module. You must enter these codes in bytes x+6 and x+7 of the channel
parameter block of data record 128 (see previous figure).
Table A- 1
Codes for output range
Value
Time period
Code
4
7
12
14
21
26
30
33
36
0.20 ms
0.40 ms
0.93 ms
1.33 ms
4.27 ms
10.67 ms
21.33 ms
34.13 ms
59.73 ms
0000 0100
0000 0111
0000 1100
0000 1110
0001 0101
0001 1010
0001 1110
0010 0001
0010 0100
Summary of Contents for DQ 4x24VDC/2A HS