Interrupts/diagnostics alarms
5.3 Diagnostics alarms
Digital output module DQ 4x24VDC/2A HS (6ES7132-6BD20-0DA0)
32
Manual, 03/2015, A5E34944434-AA
5.3
Diagnostics alarms
Diagnostics alarms
A diagnostics alarm is output for each diagnostics event and the DIAG LED flashes on the
module. The diagnostics alarms can, for example, be read from the diagnostics buffer of the
CPU. You can evaluate the error codes with the user program.
Note
You can connect 2 actuators per output.
The diagnostics of the two actuators influence each other in the case of duplicate wiring.
This means that a single short-circuit affects both actuators.
Table 5- 6
Diagnostics alarms, their meaning and corrective measures
Diagnostics alarms
Error code Meaning
Solution
Short-circuit
1
2
1
H
Short-circuit of the actuator supply
Correct the process wiring
Overtemperature
5
H
The module has detected that the maximum
permitted module temperature has been
exceeded. All channels of the module are
switched to high resistance. The module is
then restarted.
Correct the process wiring
High limit violated
7
H
The permitted value range of the duty factor
has been exceeded.
Correct the output value (0 to 1000)
Parameter assign-
ment error
10
H
•
The module cannot evaluate parameters
for the channel.
•
Incorrect parameter assignment.
Correct the parameter assignment
No load voltage
11
H
No or insufficient supply voltage L+
•
Check supply voltage L+ on the
BaseUnit
•
Check BaseUnit type
Communications
error
13
H
Module is defective.
Replace the module.
Channel temporarily
unavailable
1F
H
Firmware update in progress or update has
been canceled.
The module does not read out any process
values or substitute values in this state.
•
Wait for firmware update.
•
Restart the firmware update.
1
The channels 0 and 1 or 2 and 3 each form a load group. Within a load group, a short-circuit can have an effect on the
adjacent channel. The load groups do not have an effect on each other in the case of a short-circuit.
2
If the short-circuit persists, the module heats up. This may trigger temperature monitoring with overtemperature
diagnostic interrupt.