Parameters/address space
4.1 Parameters
Digital output module DQ 4x24VDC/2A HS (6ES7132-6BD20-0DA0)
14
Manual, 03/2015, A5E34944434-AA
Parameter
Range of values
Default
Reconfigu-
ration in
RUN
Effective range with configuration
software, e.g. STEP 7
GSD file
PROFINET IO
GSD file
PROFIBUS DP
1
Diagnostics:
Overflow
•
Disable
•
Enable
Disable
Yes
Module
Module
1
Channel activated
•
Disable
•
Enable
Enable
Yes
Channel
Channel
1
Reaction to CPU
STOP
•
Turn off
•
Keep last value
Normal operation/
Oversampling
•
Output substitute
value 1
Pulse width modulation
•
Output substitute value
Turn off
Yes
Channel
Module
1
Potential group
•
Use potential group of
the left module (dark-
colored BaseUnit)
•
Enable new potential
group (light-colored
BaseUnit)
Use potential group
of the left module
No
Module
Module
1
Holding time valve
control
•
Off
•
10 ms
•
20 ms
•
...
•
10 s
500 ms
Yes
Channel
Channel
1
Pulse width modula-
tion duty factor
•
Off
•
0.1%
•
0.2%
•
...
•
100%
100%
Yes
Channel
Channel
1