Digital output module DQ 4x24VDC/2A HS (6ES7132-6BD20-0DA0)
10
Manual, 03/2015, A5E34944434-AA
Wiring
3
3.1
Wiring and block diagram
This section includes the block diagram of the DQ 4x24VDC/2A HS module with the terminal
assignments for a 2-wire and 3-wire connection in the three operating modes DQ, pulse
width modulation and oversampling.
You can find information on wiring the BaseUnit in the ET 200SP distributed I/O system
(
http://support.automation.siemens.com/WW/view/en/58649293
) system manual.
Note
You can connect 2 actuators per output.
Note
Cross circuit at output
Be aware that voltage from a cross circuit at the output can feed L+ to modules.
Note
•
The load group of the module must begin with a light-colored BaseUnit. Keep this in mind
also during the configuration.
•
The connection of actuators with 1-wire connection is not permitted.
Note
You may use and combine the different wiring options for all channels.
Note
Outputs DQ
n
- must not be connected with ground.