7SR220 Technical Manual
Chapter 4 - Page 54 of 96
© 2017 Siemens Protection Devices Limited
DNP V3.0
DEVICE PROFILE DOCUMENT
(Also see the DNP 3.0 Implementation Table in
, beginning on page 56).
Unsolicited Notification Delay, (Configurable, default 5 seconds)
Unsolicited Response Retry Delay, (Configurable (between 3 - 9), default 5 seconds)
Unsolicited Offline Interval, (Configurable, default 30 seconds)
Binary Change Event Scan Period, (Polled, Not Applicable)
Double Bit Change Event Scan Period, (Polled - Not Applicable)
Analog Change Event Scan Period, (Polled - Not Applicable)
Counter Change Event Scan Period, (Polled - Not Applicable)
Frozen Counter Change Event Scan Period, (Polled - Not Applicable)
String Change Event Scan Period, (Unsupported - Not Applicable)
Virtual Terminal Event Scan Period, (Unsupported - Not Applicable)
Sends/Executes Control Operations:
WRITE Binary Outputs
Never
Always
Sometimes
Configurable
SELECT/OPERATE
Never
Always
Sometimes
Configurable
DIRECT OPERATE
Never
Always
Sometimes
Configurable
DIRECT OPERATE - NO ACK
Never
Always
Sometimes Configurable
Count > 1
Never
Always
Sometimes Configurable
Pulse On
Never Always
Sometimes
Configurable
Pulse Off
Never Always
Sometimes
Configurable
Latch On
Never Always
Sometimes
Configurable
Latch Off
Never Always
Sometimes
Configurable
Queue
Never
Always
Sometimes Configurable
Clear Queue
Never
Always
Sometimes
Configurable
Attach explanation if “Sometimes” or “Configurable” was checked for any operation.
Reports Binary Input Change Events when no specific
variation requested:
Never
Only time-tagged
Only non-time-tagged
Configurable to send one or the other
Reports time-tagged Binary Input Change Events when
no specific variation requested:
Never
Binary Input Change With Time
Binary Input Change With Relative Time
Configurable
Sends Unsolicited Responses:
Never
Configurable
Only certain objects
Sometimes (attach explanation)
ENABLE/DISABLE UNSOLICITED
Function codes supported
Sends Static Data in Unsolicited Responses:
Never
When Device Restarts
When Status Flags Change
No other options are permitted.
Default Counter Object/Variation:
No Counters Reported
Configurable
Default Object
Default Variation:
Point-by-point list attached
Counters Roll Over at:
No Counters Reported
Configurable (attach explanation)
16 Bits
32 Bits
Other Value:
Point-by-point list attached
Sends Multi-Fragment Responses:
Yes
No
Configurable
Sequential File Transfer Support:
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...