7SR210 Settings Guide
Unrestricted Page 20 of 61
© 2018 Siemens Protection Devices Limited
3.5.3.
Broken Conductor
Description
Range
Default
Gn 46BC U/C Guard Setting
0.05, 0.1 ... 4.95, 5
0.25 xIn
Gn 46BC U/C Guarded
No, Yes
No
Gn 46BC Element
Selects whether the definite time broken conductor element is
enabled
Disabled, Enabled
Disabled
Gn 46BC Setting
NPS Current to PPS Current ratio
20, 21 ... 99, 100
20 %
Gn 46BC Delay
Sets operate delay time
0.03, 0.04 ... 14300, 14400
20 s
3.5.4.
Trip CCT Supervision
Description
Range
Default
Gn 74TCS-1
Selects whether the trip circuit supervision element 74TCS-1
is enabled
Disabled, Enabled
Disabled
Gn 74TCS-1 Delay
Time delay before trip circuit supervision operates
0, 0.02 ... 59.98, 60
0.4 s
Gn 74TCS-2
Selects whether the trip circuit supervision element 74TCS-2
is enabled
Disabled, Enabled
Disabled
Gn 74TCS-2 Delay
Time delay before trip circuit supervision operates
0, 0.02 ... 59.98, 60
0.4 s
Gn 74TCS-3
Selects whether the trip circuit supervision element 74TCS-3
is enabled
Disabled, Enabled
Disabled
Gn 74TCS-3 Delay
Time delay before trip circuit supervision operates
0, 0.02 ... 59.98, 60
0.4 s
3.5.5.
Close CCT Supervision
Description
Range
Default
Gn 74CCS-1
Selects whether the trip circuit supervision element 74CCS-1
is enabled
Disabled, Enabled
Disabled
Gn 74CCS-1 Delay
Time delay before trip circuit supervision operates
0, 0.02 ... 59.98, 60
0.4 s
Gn 74CCS-2
Selects whether the trip circuit supervision element 74CCS-2
is enabled
Disabled, Enabled
Disabled
Gn 74CCS-2 Delay
Time delay before trip circuit supervision operates
0, 0.02 ... 59.98, 60
0.4 s
Gn 74CCS-3
Selects whether the trip circuit supervision element 74CCS-3
is enabled
Disabled, Enabled
Disabled
Gn 74CCS-3 Delay
Time delay before trip circuit supervision operates
0, 0.02 ... 59.98, 60
0.4 s
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...