7SR220 Settings Guide
Unrestricted ©2018 Siemens Protection Devices Limited
Page 51 of 107
Description
Range
Default
E4 Equation
Enable or Disable logic equation E4
Disabled, Enabled
Disabled
E4
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation.
= AND operation^ = EXCLUSIVE OR operationE(followed by a
digit) = Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed
by a digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when
function key is pressed
(requires E1 to drive L11 in output
matrix)E1 = F3^L11
(20 Character String)
E4 Pick-up Delay
Time before equation output operates, after equation satisfied
0, 0.01 ... 14300, 14400
0 s
E4 Drop-off Delay
Time before equation output resets, after equation nolonger
satisfied
0, 0.01 ... 14300, 14400
0 s
E4 Counter Target
Select number of times equation must be satisfied before
equation output operates
1, 2 ... 998, 999
1
E4 Counter Reset Mode
Select type of counter reset mode
Off, Multi-shot, Single-shot
Off
E4 Counter Reset Time
Select counter reset time
0, 0.01 ... 14300, 14400
0 s
E5 Equation
Enable or Disable logic equation E5
Disabled, Enabled
Disabled
E5
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation.
= AND operation^ = EXCLUSIVE OR operationE(followed by a
digit) = Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed
by a digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when
function key is pressed
(requires E1 to drive L11 in output
matrix)E1 = F3^L11
(20 Character String)
E5 Pick-up Delay
Time before equation output operates, after equation satisfied
0, 0.01 ... 14300, 14400
0 s
E5 Drop-off Delay
Time before equation output resets, after equation nolonger
satisfied
0, 0.01 ... 14300, 14400
0 s
E5 Counter Target
Select number of times equation must be satisfied before
equation output operates
1, 2 ... 998, 999
1
E5 Counter Reset Mode
Select type of counter reset mode
Off, Multi-shot, Single-shot
Off
E5 Counter Reset Time
Select counter reset time
0, 0.01 ... 14300, 14400
0 s
E6 Equation
Enable or Disable logic equation E6
Disabled, Enabled
Disabled
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...