7SR220 Settings Guide
Unrestricted Page 16 of 107
© 2013 Siemens Protection Devices Limited
Description
Range
Default
Gn 50-1 Inrush Action
Selects if the 50-1 element is blocked from operating when
2nd Harmonic Inrush Detector operates
Off, Inhibit
Off
Gn 50-1 21LB-3P Action
Selects if operation of the 50-1 element is blocked for defined
load conditions
Off, Inhibit
Inhibit
Gn 50-1 21LB-1P Action
Selects if operation of the 50-1 element is blocked for defined
load conditions
Off, Inhibit
Off
3.4.1.6.
50-2
Description
Range
Default
Gn 50-2 Element
Selects whether the INST/ DTL Overcurrent element is
enabled
Disabled, Enabled
Disabled
Gn 50-2 Dir. Control
Selects whether 50-2 element is non-directional, forward or
reverse
Non-Dir, Forward, Reverse
Non-Dir
Gn 50-2 Setting
Pickup level
0.05, 0.06 ... 49.5, 50
1 xIn
Gn 50-2 Delay
Sets operate delay time
0, 0.01 ... 14300, 14400
0 s
Gn 50-2 VTS Action
Selects whether 50-2 element is blocked or made non-
directional when VTS operates
Off, Inhibit, Non-Dir
Off
Gn 50-2 Inrush Action
Selects if the 50-2 element is blocked from operating when
2nd Harmonic Inrush Detector operates
Off, Inhibit
Off
Gn 50-2 21LB-3P Action
Selects if operation of the 50-2 element is blocked for defined
load conditions
Off, Inhibit
Inhibit
Gn 50-2 21LB-1P Action
Selects if operation of the 50-2 element is blocked for defined
load conditions
Off, Inhibit
Off
3.4.1.7.
50-3
Description
Range
Default
Gn 50-3 Element
Selects whether the INST/ DTL Overcurrent element is
enabled
Disabled, Enabled
Disabled
Gn 50-3 Dir. Control
Selects whether 50-3 element is non-directional, forward or
reverse
Non-Dir, Forward, Reverse
Non-Dir
Gn 50-3 Setting
Pickup level
0.05, 0.06 ... 49.5, 50
1 xIn
Gn 50-3 Delay
Sets operate delay time
0, 0.01 ... 14300, 14400
0 s
Gn 50-3 VTS Action
Selects whether 50-3 element is blocked or made non-
directional when VTS operates
Off, Inhibit, Non-Dir
Off
Gn 50-3 Inrush Action
Selects if the 50-3 element is blocked from operating when
2nd Harmonic Inrush Detector operates
Off, Inhibit
Off
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...