Setting name
Range
Default
Units
Notes
Station Address
1 – 254 for IEC60870-5-103
0 – 247 for Modbus RTU
0 – 65520 for DNP3.0
0
Address given to relay to
identify that relay from
others which may be using
the same path for
communication as other
relays for example in a fibre
optic hub
COM1-RS485 Protocol
OFF, IEC60870-5-103,
MODBUS-RTU, DNP3.0
IEC60870-5-
103
COM1 is the rear mounted
RS485 port
COM1-RS485 Baud
Rate
75 110 150 300 600 1200
2400 4800 9600 19200
38400
19200
COM1-RS485 Parity
NONE, ODD, EVEN
EVEN
COM2-USB Protocol
OFF, IEC60870-5-103,
DNP3.0, MODBUS-RTU,
ASCII
IEC60870-5-
103
COM2 is the front USB port
COM2-USB Baud Rate
75 110 150 300 600 1200
2400 4800 9600 19200
38400 57600 115200
230400 460800 921600
Auto detects
Auto detects baud rate via
Connection Manager Setting
COM2-USB Parity
NONE, ODD, EVEN
EVEN
COM3 Protocol
OFF, IEC60870-5-103,
MODBUS-RTU, DNP3.0
IEC6-0870-5-
103
COM3 This is an optional
rear mounted connection
COM3 Baud Rate
75 110 150 300 600 1200
2400 4800 9600 19200
38400 57600 115200
57600
COM3 Parity
NONE, ODD, EVEN
EVEN
COM3 Line Idle*
LIGHT ON, LIGHT OFF
LIGHT OFF
COM3 Data echo*
ON, OFF
OFF
COM4 Protocol**
OFF, IEC60870-5-103,
MODBUS-RTU, DNP3.0
OFF
COM4 This is an optional
rear mounted connection
COM4 Baud Rate**
75 110 150 300 600 1200
2400 4800 9600 19200
38400
19200
COM4 Parity**
NONE, OFF, EVEN
EVEN
COM4 Line Idle**
LIGHT ON, LIGHT OFF
LIGHT OFF
COM4 Data echo**
ON, OFF
OFF
DNP3 Unsolicited
Events
ENABLED, DISABLED
DISABLED
Setting is only visible when
a port protocol is set to
DNP3.
DNP3 Destination
Address
0 … 65534
0
Setting is only visible when
a port protocol is set to
DNP3.
DNP3 Application
Timeout
5, 6 ... 299, 300
10s
Secon
ds
Setting is only visible when
a port Protocol is set to
DNP3
*Not applicable for RS485 or RS232 interface modules.
**Fibre Optic Module only
Summary of Contents for Argus 7SR21
Page 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Page 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Page 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Page 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Page 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Page 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Page 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Page 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Page 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Page 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Page 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Page 643: ...Unrestricted ...