7SG11 Argus 8 Appendix
FREQUENCY MENU
SETTING RANGE
SET
VALUE
Gn F Element 1 Operation
OFF, O/F, U/F
Gn F Element 1 Setting
47.00Hz – 62.00Hz step 0.01Hz
Gn F Element 1 Delay
0.00 – 20.00 step 0.01 sec
20.0 – 100.0 step 0.5 sec
100 – 600 step 1.0 sec
Gn F Element 1 Inhib
VE1, VE2, VE3, VE4
Gn F Element 2 Operation
OFF, O/F, U/F
Gn F Element 2 Setting
47.00Hz – 62.00Hz step 0.01Hz
Gn F Element 2 Delay
As Element 1 Delay
Gn F Element 2 Inhib
VE1, VE2, VE3, VE4
Gn F Element 3 Operation
OFF, O/F, U/F
Gn F Element 3 Setting
47.00Hz – 62.00Hz step 0.01Hz
Gn F Element 3 Delay
As Element 1 Delay
Gn F Element 3 Inhib
VE1, VE2, VE3, VE4
Gn F Element 4 Operation
OFF, O/F, U/F
Gn F Element 4 Setting
47.00Hz – 62.00Hz step 0.01Hz
Gn F Element 4 Delay
As Element 1 Delay
Gn F Element 4 Inhib
VE1, VE2, VE3, VE4
©2010 Siemens Protection Devices Limited
Chapter 9 Page 5 of 13