7SG11 Argus 8 Relay Settings
The following two menus appear if the ‘2 Systems A/B’ option is selected. They replace the Voltage Menu.
3 System A Menu
SETTING RANGE
DEFAULT
Gn V Element 1 Operation
sets the mode of operation of Voltage Element 1,
whether under or over-voltage
OFF, O/V, U/V
OFF
Gn V Element 1 Setting
sets the pickup level of Voltage Element 1
5V – 200V step 0.5V
80V
Gn V Element 1 Delay
sets the DTL timer value for Voltage Element 1
0.00 – 20.00 step 0.01 sec
20.0 – 100.0 step 0.5 sec
100 – 600 step 1.0 sec
0.00 sec
Gn V Element 1 Hysteresis
sets the amount of hysteresis required i.e. the
PU/DO ratio
1% – 90% step 1%
2%
Gn V Element 2 Operation
As per Element 1
OFF
Gn V Element 2 Setting
As per Element 1
80V
Gn V Element 2 Delay
As per Element 1
0.00 sec
Gn V Element 2 Hysteresis
As per Element 1
2%
4 System B Menu
SETTING RANGE
DEFAULT
Gn V Element 3 Operation
sets the mode of operation of Voltage Element 3,
whether under or over-voltage
OFF, O/V, U/V
OFF
Gn V Element 3 Setting
sets the pickup level of Voltage Element 3
5V – 200V step 0.5V
80V
Gn V Element 3 Delay
sets the DTL timer value for Voltage Element 3
0.00 – 20.00 step 0.01 sec
20.0 – 100.0 step 0.5 sec
100 – 600 step 1.0 sec
0.00 sec
Gn V Element 3 Hysteresis
sets the amount of hysteresis required i.e. the
PU/DO ratio
1% – 90% step 1%
2%
Gn V Element 4 Operation
As per Element 1
OFF
Gn V Element 4 Setting
As per Element 1
80V
Gn V Element 4 Delay
As per Element 1
0.00 sec
Gn V Element 4 Hysteresis
As per Element 1
2%