7SG11 Argus 8 Relay Settings
©2010 Siemens Protection Devices Limited
Chapter 3 Page 9 of 10
SETTING RANGE
DEFAULT
Gn Clock Sync.
sets the status input(s) which, on energisation, will
synchronise the real time clock to the nearest
second or minute
S1..Sn None
Gn Reset Outputs
sets the status input(s) which, on energisation, will
reset the Trip LED and any latched output relays
S1..Sn None
Gn Status 1 P/U Delay
sets the delay period to be applied to the pick-up of
Status Input 1
0 – 2.00 sec step 10ms
2.10 – 20.00 sec step 100ms
21 – 300 sec step 1 sec
360 – 3600 sec step 60 sec
3900 – 14400 sec step 300 sec
0.02sec
Gn Status 1 D/O Delay
sets the delay period to be applied to the drop-off of
Status Input 1
As above
0.00sec
Gn Status n P/U Delay
As Status 1
0.02sec
Gn Status n D/O Delay
As Status 1
0.00sec
10
Comms Interface Menu
SETTING RANGE
DEFAULT
Comms Protocol
IEC60870-5-103,
MODBUS-RTU
IEC60870-5-
103
Class 2 Update Period
INST, 1 – 60 sec
15 sec
IEC Class 2 Scaling
1.2x, 2.4x
1.2x
Comms Baud Rate
sets the required communications Baud Rate
75, 110, 150, 300, 600, 1200, 2400,
4800, 9600, 19200
19200
Comms Parity
selects whether a parity check is transmitted with
the comms data
NONE, EVEN
EVEN
Relay Address
sets the required address of a particular relay within
a network
0 – 254
0
Line Idle
sets the required communications line idle sense
LIGHT ON, LIGHT OFF LIGHT
OFF
Data Echo
enables Data Echo which is necessary for use with
relays connected in a ring
OFF / ON
OFF
11
Data Storage Menu
SETTING RANGE
DEFAULT
Gn Fault Trigger
sets the output relay(s) which are connected as trip
outputs for the purpose of giving trip information and
storing fault records
RL1..RLn None
Gn Waveform Trig
selects which functions trigger a waveform record
STA, V, F, NPS, NVD
STA+V+NPS+
NVD+F
Gn Waveform Pre-trigger
selects which functions trigger a waveform record
OFF, 10%-100% step 10%
50%