7SG11 Argus 8 Description of Operation
Function
Terminal
Terminal
Function
Va / (Vab)
Start
1 2
Finish
Va / (Vab)
Vo / (Vbc)
Start
3 4
Finish
Vo / (Vbc)
Status Input 1
(+)
5 6
(–)
Status Input 1
Relay 1 (N/C)
–
7 8
– Relay
1
(N/C)
Relay 2 (N/O)
–
9 10
– Relay
2
(N/O)
Relay 4 (N/O)
–
11 12
– Relay
4
(N/O)
Aux. Volts
(+)
13 14
(–) Aux.
Volts
Earth
15 16
– Relay
3
(N/O)
Relay 3 (COM)
–
17 18
– Relay
3
(N/C)
Relay 5 (N/O)
–
19 20
– Relay
5
(N/O)
Relay 6 (N/O)
–
21 22
– Relay
6
(N/O)
Relay 7 (N/O)
–
23 24
– Relay
7
(N/O)
Status Input 4
(+)
25 26
(+)
Status Input 3
T
erminal Bl
ock
1
Status Input 2
(+)
27 28
(–) Status
Common
Table 4 - Connection Table (E4 Versions)
©2010 Siemens Protection Devices Limited
Chapter 1 Page 16 of 20