Technical specifications
6.4 Derating and temperature compensation
3VA molded case circuit breakers
492
Manual, 04/2015, A5E03603177010-02
Using the setting factor calculated at 50 °C, it is possible to read the correction factor K off
the following charts:
No derating up to the rated operational current I
n
of the molded case circuit breaker
Using the two calculated values, it is possible to determine the temperature compensation
TK and finally the setting value for the trip unit I
r(TU)
:
TK(T
U
) Temperature compensation for molded case circuit breaker with service tempera-
ture T
U
K
Correction factor
T
u
Service temperature of molded case circuit breaker
Trip unit setting value:
I
r(TU)
= I
n
· EF(50 °C) · TK
I
r(TU)
Trip unit setting value with service temperature T
u