Applications
3.1 Line protection applications of 3VA molded case circuit breakers
3VA molded case circuit breakers
112
Manual, 04/2015, A5E03603177010-02
Electronic trip unit ETU330 LIG
ETU330 LIG 3-pole:
ETU330 LIG 4-pole:
Line protection - function LIG
The electronic trip unit ETU330 has:
●
adjustable parameter settings I
r
and t
r
for overload protection (L)
●
adjustable parameter setting I
i
for instantaneous short-circuit protection (I)
●
adjustable parameter settings I
g
and t
g
for ground-fault protection (G)
●
With 4-pole versions only: Neutral conductor protection (N) which can be deactivated