Technical specifications
6.4 Derating and temperature compensation
3VA molded case circuit breakers
Manual, 04/2015, A5E03603177010-02
489
6.4
Derating and temperature compensation
6.4.1
Derating of 3VA1 molded case circuit breakers
The temperature inside the molded case circuit breaker is influenced by the ambient
temperature and the current-dependent power loss generated inside the unit. To prevent
overloading of 3VA1 molded case circuit breakers under difficult thermal conditions, the
maximum rated continuous operational current must be limited as a function of the ambient
temperature.
No derating up to the rated operational current I
n
of the molded case circuit breaker
Note
These values do not apply to all mounting conditions for molded case circuit breakers and
may deviate depending upon factors such as cables and busbars, packing density,
ventilation, etc.
Please observe the applicable overriding guidelines (e.g. IEC 61439).