Functions of the Terminal
The displayed unit of the current depends on the DeviceDriveFunctionMode: For “Ser-
vo” and “HSBLOCK”, the current is displayed as sine wave peak amplitude (A), for
“HSPWM”, “HSPAM” und “U/f” as RMS value (Arms).
The input value will be checked with regard to its limits. In case of an error, a correspond-
ing error message will be displayed during one second and then you can enter the value
again.
14.3.3
SAVE PARAMETER
Note
You must enter the correct password to open this menu item.
Once you entered your password, the object data will be transferred into the initialization
paremeters and the check sum will be recalculated.
The following object data are transferred:
▶
Acceleration ramp time (object 186)
▶
Deceleration ramp time (object 187)
▶
Quick stop ramp time (object 188)
▶
W24 load warning threshold (object 95)
▶
W26 overload current (object 400)
▶
Internal setpoints (object 406)
▶
Motor potentiometer step size (object 410)
In a next step, the drive is switched to the loader. Then, the initialization parameters are
written to the Flash Eeprom and the drive is set back to the firmware mode. The following
display is shown:
Finally, the operating terminal switches to the actual value display of the automatic op-
eration.
14.3.4
SELECT PARAMSET
Note
You must enter the correct password to open this menu item. Futhermore, the method
for parameter set selection in the drive data must be set to “Fixed selection (EEPROM)”.
If the selection method is “Digital inputs” or “Field bus”, you cannot change the parame-
ter set via the operating terminal. In this case, the error message “Function not allowed”
will be displayed for one second and the terminal will switch to the actual value display.
If changing the parameter set is allowed, you must enter the correct password before
you can select the desired parameter set.
32
Drive System SD2x - Operating Terminal 0362150 and 0362153