ERROR BEHAVIOR
8022483/108R/2018-07-09 | SICK
SAFETY-RELATED 2D LIDAR SENSOR | TIM361S
35
Subject to change without notice
0.05 m from the measurement origin of the TIM361S, causing impairment,
reduction or complete loss of detection capability, and the device no longer being
able to perform the safety function.
DANGER
Risk of ineffectiveness of the protective device
Undetected errors and faults of the TiM361S can cause impairment, reduction or
complete loss of detection capability, such that the device is no longer able to perform
the safety function.
NOTE
As per EN ISO 13849-1 PL b, the sensor has diagnostic coverage (DC) of zero, i.e., it
must not detect errors and if they occur, can result in loss of the
safety functions.
Testing and diagnostic measures can identify errors, such as those of the downstream
controller.
6.4
Fault exclusions
No fault exclusions have been specified for the sensor. The occurrence of faults can
result in the loss of the
safety function
.
6.5
Manipulation
The device does not have any protective measures against manipulation, especially
none that relate to the optical system. Objects, especially covering objects on the optics
cover and/or in the blind zone, are not detected by the TiM361S, causing impairment,
reduction or complete loss of detection capability, and the device no longer being able
to perform the safety function.
Manipulations with effects similar to undetected faults (see chapter 6.3 "Undetected
errors and faults") are also not detected.