The device can be configured so that the desired output values are output in a
continuous data stream or on request:
•
During “continuous data output”, the distance sensor provides distance values or
selected combined data to the interface at defined intervals. The data output is
started automatically after switching on the supply voltage. If the device has been
configured for “data output on request”, continuous data output is started as soon
as the desired output value (distance or combined values) is selected.
•
During “data output on request”, the measured values are only transmitted to
the controller on request. Continuous data transmission in this case must be
deactivated by selecting “REQ”.
Parameter
Factory setting
Off:
No continuous data output; data output active on request
Off
Distance:
Continuous output of distance values
Di speed:
Continuous output of distance and speed values
Di service:
Continuous output of distance values and service data
Di signal level (RSSI):
Continuous output of distance and signal level values
8.5.5
Defining the RS-422 output cycle time
Define the output cycle time of the data to be transmitted for continuous data output
over the serial interface.
The output cycle time should not be shorter than the set measurement cycle time,
since otherwise several identical values are output between two subsequent measure‐
ment cycles.
The minimum achievable output cycle time depends on the data transmission rate,
the RS-422 data protocol (STX/ETX or CRLF) and the selected output value (distance,
dspeed etc.),
see "RS-422 interface", page 20
. If a shorter output cycle time is
set, output is done in accordance with the values specified in
.
Parameter
Factory setting
Output cycle time:
0 ms ... 1,000 ms
1 ms
REFERENCE
8
8024560/1A19/2021-06-30 | SICK
O P E R A T I N G I N S T R U C T I O N S | DT1000 PROFIBUS DP and DL1000 PROFIBUS DP
83
Subject to change without notice