![SICK CLV69x Operating Instructions Manual Download Page 77](http://html.mh-extra.com/html/sick/clv69x/clv69x_operating-instructions-manual_1264249077.webp)
6
1
10
5
11
15
6
1
10
5
11
15
Wire supply voltage for CLV69x-xxx0 in the CDM490-0001 connection module
CDM490-0001
(basic card)
U
V
U
V
U
V
= DC 18 ... 30 V
1
5
1
5
5
Shield
1
+24 V
2
GND
+24 V*
GND
S1
F
Shield
D-Sub-HD
D-Sub-HD
Cable 1, e.g. no. 2020302 (3 m)
Cable 2, e.g. no. 2020302 (3 m)
GND
.
.
.
.
.
.
.
.
.
1
5
1
5
.
.
.
.
.
.
.
.
.
ON
OFF
S1 : POWER
+24 V*
POWER
+) If no switching inputs and outputs of the CLV69x are used, cable 2 does not have to be used
10 5
6
1
15
11
10 5
6
1
15
11
1
2
1
“HOST/AUX/I/O” connection
2
“I/O” connection
CLV69x-xxx0
(without heating)
DC 18 V ... 30 V
Max.
2 A
F
U
V
= DC 18 V ... 30 V at te24 V =
U
V
at te24 V* after switch S1, protected by internal fuse F
Switch S1:
ON:
supply voltage U
V
(+24 V) switched via fuse as U
V
(+24 V*)
to CDM490-0001 and CLV69x.
U
V
(+24 V*) can also be engaged on terminal 29 of the basic
card as well as on terminal 51 ... 53 of the I/O card.
OFF:
CDM490-0001 and CLV69x separated from supply voltage.
Recommended position for all connection types.
Figure 70: Wire supply voltage for CLV69x-xxx0 (without heating)
ELECTRICAL INSTALLATION
6
8014396/ZMG8/2017-07-04 | SICK
O P E R A T I N G I N S T R U C T I O N S | CLV69x
77
Subject to change without notice