5
Mounting
5.1
Required materials
You need the following additional materials to mount the device:
•
grounded mounting rail (pre-mounted)
•
pre-assembled cable (max. 30 m) with M8 female connector (
)
•
pre-assembled cable for PROFINET with M12 D-coded male connector (
•
one or more signal sources (e.g. WLL180T)
•
small slotted screwdriver
5.2
Preparing mounting location
1.
Mount a grounded mounting rail in the same area as the application.
2.
Lay the two pre-assembled cables so that they can easily be connected to the con‐
nections of the device. If necessary, use cable channels, cable ties and cable
grips.
5.3
Scope of delivery
•
WI180C-PN
•
Quick start instructions
5.4
Mounting procedure
1.
Carefully unpack the device.
1
2
2.
Clamp the device onto the mounting rail, as shown in the image.
3.
Clamp the series-connected devices onto the mounting rail as shown in their
mounting instructions.
MOUNTING
5
8023551/11HP/2019-03-07 | SICK
O P E R A T I N G I N S T R U C T I O N | WI180C-PN
11
Subject to change without notice