Value
LEDs
PWR, BF/ERR/NS, SF/RUN/MS, STATUS, L/A1, L/A2
Power supply
Male M8 plug connector, 4-pin
Other interfaces
Male bus connector, 5-pin, internal system bus
2 x M12 4-pin D-coded, PROFINET
PROFINET IO
Table 12: PROFINET IO data
Description
Value
Maximum number of mod‐
ules to be connected
16
Transmission speed
100 MBit/s
Maximum distance
between nodes
100 m
Process data
Depending on selected modules
Max. 44 bytes input, 4 bytes output
Min. cycle time 1 ms
Asynchronous data
supported,
Compliant standard
IEEE802.3u (100Base-Tx)
Conformance class
Class C (PROFINET IRT)
Netload class
III
Ethernet ports
2
PROFINET features
Media Redundancy (MRP),
network diagnostic (MIB/SNMP),
topology detection,
port diagnostic (Up/Down),
connection diagnostic (connection length measurement),
I&M0...4,
auto device replacement,
reduction ratio,
openVAS tested
GSD file
available (V2.2, V2.32, V2.33, V2.34)
EMC
Table 13: EMC data
Description
Value
Noise immunity (Length of
cable ≤30 m)
in accordance with EN 61000-6-2/ EN 61131-2
Emission
in accordance with EN 55011, class A
Product safety
Table 14: Product safety data
Description
Value
Protection class
3
Short-circuit protection
in accordance with VDE 0160
10